Analysis of lightning impulse voltage distribution for a dry-type transformer using three different winding types

Yükleniyor...
Küçük Resim

Tarih

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Elsevier Sci Sa

Erişim Hakkı

info:eu-repo/semantics/embargoedAccess

Özet

In this study, simulation and test results for lightning impulse voltage distribution in a dry-type transformer were compared for three different winding methods by using round, flat, and strip conductors. Distribution of the voltage inside the transformer windings at high frequencies had a different behavior than that of at low frequencies. The transformer had non-linear voltage distributions at high frequencies due to the inner capacitance and inductance of its windings. The ladder network model was used for the analysis of high frequency signals for voltage distribution. The parameters of the model were calculated analytically and numerically using a finite element analysis (FEA) software. The analytical solution method of a matrix obtained from the ladder network model was presented. Finally, simulation and test results were given and compared.

Açıklama

Eker, Mehmet Kubilay (Balikesir Author)

Anahtar Kelimeler

Lightning Impulse, Dry Type Transformer, Transformer Winding Modelling, Transient Simulation, Lumped Parameters, Distributed Parameters

Kaynak

Electric Power Systems Research