Assessment of thermodynamic and environmental performances in subcooling process for different refrigerants

dc.authorid0000-0001-9271-1309en_US
dc.authorid0000-0001-671-1955en_US
dc.contributor.authorAltuntaş, Önder
dc.contributor.authorSöğüt, M. Ziya
dc.contributor.authorYalçın, Enver
dc.contributor.authorKarakoç, T. Hikmet
dc.date.accessioned2019-10-03T08:11:47Z
dc.date.available2019-10-03T08:11:47Z
dc.date.issued2017en_US
dc.departmentFakülteler, Mühendislik Fakültesi, Makine Mühendisliği Bölümüen_US
dc.descriptionYalçın, Enver (Balikesir Author)en_US
dc.description.abstractSubcooling application in cooling processes leads to increasing of cooling performance and energy efficiency within defined limits. This study examines subcooling effects of refrigerants on the coefficient of performance (COP), exergy efficiency and environmental performances based on total equivalent warming impact (TEWI) and human health damage (HDD), which are considered environmental parameters, by considering different refrigerants. In the analyses, direct expansion (DX) system, which is used commonly in supermarkets, and the evaporator temperatures of the system 238 and 273 K are taken as reference. In addition, current refrigerants R-22, R-404A and R-507 and the alternative refrigerant R-407C are examined separately. The results of analyses show that the subcooling of 5 K in condenser causes energy saving between 4% and 8% as depending on the refrigerants and provides an increase as the exergy efficiency between 3% and 25%. Besides, HDD and TEWI values also decrease with increasing of subcooling temperature. At the end of the study, effect on system performance of subcooling processes was emphasised as related to exergy and TEWI analyses.en_US
dc.identifier.doi10.1504/IJEX.2017.10008597
dc.identifier.endpage234en_US
dc.identifier.issue2-4en_US
dc.identifier.scopus2-s2.0-85032683259
dc.identifier.scopusqualityQ3
dc.identifier.startpage216en_US
dc.identifier.urihttps://hdl.handle.net/20.500.12462/6657
dc.identifier.volume24en_US
dc.identifier.wosWOS:000414955200007
dc.identifier.wosqualityQ4
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoenen_US
dc.publisherInderscience Enterprises Ltden_US
dc.relation.ispartofInternational Journal of Exergyen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectDX Systemsen_US
dc.subjectCOPen_US
dc.subjectCoefficient Of Performanceen_US
dc.subjectRefrigerantsen_US
dc.subjectExergy Analysesen_US
dc.subjectCO2 Emissionen_US
dc.titleAssessment of thermodynamic and environmental performances in subcooling process for different refrigerantsen_US