On the no-load loss of power transformers under voltages with sub-harmonics
Dosyalar
Tarih
Yazarlar
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Erişim Hakkı
Özet
Power transformers are traditionally designed for their utilization in sinusoidal voltage and current conditions. However, the non-linear loads are largely proliferated in the modern power systems. Thus, pcc (point of common coupling) voltages and line currents usually have harmonically distorted or non-sinusoidal waveshapes. This study focuses on the parametrical analysis of transformer no-load loss under the excitation voltage with several sub-harmonic contents. For this aim, a computationally efficient technique is developed by combining both the harmonic-domain model of transformer windings and Finite Element Method (FEM) based modeling of transformer core. The obtained simulation results figured out that effect of sub-harmonic voltages on the transformer core loss is negligible. However, it is also seen that small amount of sub-harmonic voltages may highly contribute the winding loss under the no-load condition, and they should carefully be handled for the derating of power transformers.