Investigation of heat recovery potential according to flue gas field measurements in solid fuel-fired buildings with district and central heating systems

dc.authorid0000-0002-5166-0258en_US
dc.authorid0000-0003-1232-649Xen_US
dc.contributor.authorKon, Okan
dc.contributor.authorCaner, İsmail
dc.date.accessioned2023-07-26T07:44:35Z
dc.date.available2023-07-26T07:44:35Z
dc.date.issued2022en_US
dc.departmentFakülteler, Mühendislik Fakültesi, Makine Mühendisliği Bölümüen_US
dc.description.abstractIn this study, flue gas heat recovery potential was determined by using the flue gas measurements from boilers of buildings with solid fuel-fired district and central heating systems in Balikesir, Turkey. Potential flue gas heat recovery potential in terms of energy savings were examined. The potential of heating the preheated water and combustion air supplied to the boiler was analyzed. Thus, the efficiency of the heating system was increased, and energy savings were achieved by providing fuel savings. In order to reduce the flue gas temperature in solid fuel-fired boilers, the acidification temperature, fuel properties and excess air coefficient should be known. Below the acidification temperature, corrosion and other adverse effects may occur in the flue and in the heat exchanger. In this study, acidification temperature and fuel and combustion characteristics of coal were taken into account. Generally, seven types of coal are used for heating purposes in Balikesir province. Thus, flue gas heat recovery potential was determined for these seven types of coal. In terms of energy savings, the recovery potential in Balikesir province was calculated to be between 287,706 and 152,780 kW.en_US
dc.identifier.doi10.3390/pr10102040
dc.identifier.endpage18en_US
dc.identifier.issn2227-9717
dc.identifier.issue10en_US
dc.identifier.scopus2-s2.0-85140842004
dc.identifier.scopusqualityQ2
dc.identifier.startpage1en_US
dc.identifier.urihttps://doi.org/10.3390/pr10102040
dc.identifier.urihttps://hdl.handle.net/20.500.12462/13250
dc.identifier.volume10en_US
dc.identifier.wosWOS:000875952000001
dc.identifier.wosqualityQ2
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoenen_US
dc.publisherMDPIen_US
dc.relation.ispartofProcessesen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.rights.urihttp://creativecommons.org/licenses/by/3.0/us/*
dc.subjectChimney Gas Temperatureen_US
dc.subjectHeat Recoveryen_US
dc.subjectAcid Dew Point Temperatureen_US
dc.subjectAir Excess Coefficientsen_US
dc.subjectLignite Coalen_US
dc.titleInvestigation of heat recovery potential according to flue gas field measurements in solid fuel-fired buildings with district and central heating systemsen_US
dc.typeArticleen_US

Dosyalar

Orijinal paket

Listeleniyor 1 - 1 / 1
Yükleniyor...
Küçük Resim
İsim:
okan-kon6.pdf
Boyut:
4.8 MB
Biçim:
Adobe Portable Document Format
Açıklama:
Tam Metin / Full Text

Lisans paketi

Listeleniyor 1 - 1 / 1
Yükleniyor...
Küçük Resim
İsim:
license.txt
Boyut:
1.44 KB
Biçim:
Item-specific license agreed upon to submission
Açıklama: