Life cycle assessment of energy-efficient improvement for external walls of hospital building

Yükleniyor...
Küçük Resim

Tarih

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Inderscience Enterprises Ltd

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

In this study, life cycle assessment analysis was examined for the insulation material applied to the external walls in hospital building in Balikesir. Optimum insulation thicknesses were calculated depending on different insulation materials such as glass wool, rock wool and polyurethane considering the combustion properties. Then, the life cycle saving (LCS) and life cycle total cost (LCT) values were calculated based on the energy consumption of the uninsulated and optimally insulated external wall for ten years life. Finally, CO2 emission savings due to life cycle greenhouse gas (LCG) were estimated. Optimum insulation thicknesses were found to be 0.157 m for glass wool, 0.074 m for rock wool and 0.022 m for polyurethane.

Açıklama

Anahtar Kelimeler

Hospital Building, Optimum Insulation Thickness, Life Cycle Assessment, Greenhouse Emission