Gelişmiş Arama

Basit öğe kaydını göster

dc.contributor.authorAslan, Asiye
dc.contributor.authorYüksel, Bedri
dc.contributor.authorAkyol, Tuğrul
dc.date.accessioned2019-10-17T10:57:46Z
dc.date.available2019-10-17T10:57:46Z
dc.date.issued2014en_US
dc.identifier.issn0196-8904
dc.identifier.issn1879-2227
dc.identifier.urihttps://doi.org/10.1016/j.enconman.2013.12.066
dc.identifier.urihttps://hdl.handle.net/20.500.12462/8337
dc.description.abstractIn this paper, the effects of different operating conditions of the Gonen geothermal district heating system (GDHS) on its annual energy and exergy performance are investigated. The system parameters such as temperature, pressure and flow rate are monitored by using fixed and portable measuring instruments over a one-year period. Thus the main differences in the annual system operation are detected. The measurements show that the Gonen GDHS has six different operating cases depending on the outside temperature throughout the year. The energy and exergy analysis of the system is carried out for each case using the actual system parameters at the corresponding reference temperatures, which are 3.86, 7.1, 8:88, 11.83, 15.26 and 20.4 degrees C. The highest and lowest energy (57.32%, 35.64%) and exergy (55.76%, 41.42%) efficiencies of the overall system are calculated at the reference temperatures of 15.26 C and 3.86 degrees C, respectively. Besides, taking the six case-based energy and exergy analyses into account, the annual average energy and exergy efficiencies are determined to be 45.24% and 47.33%, respectively.en_US
dc.description.sponsorshipTUBITAK (The Scientific and Technological Research Council of Turkey)en_US
dc.language.isoengen_US
dc.publisherPergamon-Elsevier Science Ltden_US
dc.relation.isversionof10.1016/j.enconman.2013.12.066en_US
dc.rightsinfo:eu-repo/semantics/embargoedAccessen_US
dc.subjectGeothermal Energyen_US
dc.subjectPerformance Analysisen_US
dc.subjectDistrict Heating Systemen_US
dc.titleEffects of different operating conditions of Gonen geothermal district heating system on its annual performanceen_US
dc.typearticleen_US
dc.relation.journalEnergy Conversion and Managementen_US
dc.contributor.departmentGönen Meslek Yüksekokuluen_US
dc.identifier.volume79en_US
dc.identifier.startpage554en_US
dc.identifier.endpage567en_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US


Bu öğenin dosyaları:

Thumbnail

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster