dc.date.submitted2017en
dc.identifier.citationBaskın, Niyazi. Bir soğuk hava deposunda farklı kontrol yöntemlerinin enerji verimliliği yönüyle karşılaştırmalı analizi. Yayınlanmamış yüksek lisans tezi. Balıkesir Üniversitesi Fen Bilimleri Enstitüsü, 2017.en_US
dc.identifier.urihttps://hdl.handle.net/20.500.12462/3086
dc.descriptionBalıkesir Üniversitesi, Fen Bilimleri Enstitüsü, Makina Mühendisliği Ana Bilim Dalıen_US
dc.description.abstractGünümüzde Dünya elektrik enerjisi tüketiminde, küçük kapasiteli uygulamalardan, büyük kapasiteli endüstriyel ve ticari uygulamalara kadar geniş alanı kapsayan soğutma ve iklimlendirme sistemlerinin payı oldukça yüksektir. Soğutma sistemlerinde yapılacak iyileştirmeler ve verimlilik çalışmaları ile önemli ölçüde kazanç sağlamak mümkündür. Bu çalışmada mekanik buhar sıkıştırmalı soğutma çevriminde çalıştırılan soğutma sistem cihazları üzerinde farklı kontrol yöntemleri deneysel olarak uygulanarak enerji tüketimleri hesaplanıp, verimlilik yönünden karşılaştırmalar yapılmıştır. Soğuk depo iç sıcaklıkları olarak -5°C,-3°C, -1°C, +1°C, +3°C, +5°C ve her sıcaklık değeri için uygulanan %4, %8, %12, %16, %20 oranlarındaki iç ısı yükleri, iki konumlu (açık-kapalı) ve PI (Oransal+İntegral) kontroller için ayrı ayrı uygulanmıştır. 9 farklı noktadan sıcaklık, 6 farklı noktadan basınç değerleri ölçülmüştür. Kompresör, kondenser ve evaporatörün tükettiği güç değerleri 10 saniye zaman aralıkları ile eş zamanlı ölçülmüş ve bilgisayara kaydedilmiştir. Deney sonucunda PI kontrol yönteminin, iki konumlu kontrol yöntemine göre enerji verimliliği açısından daha üstün olduğu tüketilen güç hesaplamaları ile görülmüştür.en_US
dc.description.abstractThe refrigeration and air-conditioning systems used in industrial and commercial application areas with small or large capacity have a considerable share of world energy consumption. In this study, the energy consumption of refrigeration system that working based on vapour compression was measured by using different control mechanisms and was analysed comparatively in terms of productivity. The heat loads of %4, %8, %12, %16, %20 were applied for control methods that had two positions (open-closed) and for PI (Proportional + Gntegral) under the cold store temperatures of -5°C, -3°C, -1°C, +1°C, +3°C, +5°C, separately. The temperatures were measured at nine different points while pressure levels were measured at six different points. The power values consumed by the compressor, condenser and evaporator were measured synchronically in 10 second intervals and were recorded to computer. The experiments based on the consumed energy calculations showed that PI control mechanism is superior to two positions control mechanism in terms of energy productivity.en_US
dc.language.isoturen_US
dc.publisherBalıkesir Üniversitesi Fen Bilimleri Enstitüsüen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectSoğuk depoen_US
dc.subjectKontrol sistemlerien_US
dc.subjectEnerji verimliliğien_US
dc.subjectCold roomen_US
dc.subjectControl systemen_US
dc.subjectEnergy efficiencyen_US
dc.titleBir soğuk hava deposunda farklı kontrol yöntemlerinin enerji verimliliği yönüyle karşılaştırmalı analizien_US
dc.title.alternativeComparative analysis of different control methods with energy effiency aspects in a cold storeen_US